Voltage Drop Calculator

Estimate the voltage lost along a cable run from the wire size and material, supply voltage, current and length, in AWG or mm², for single-phase, DC and three-phase circuits.

Voltage drop calculator
Wire size standard
Voltage drop

    Uses the NEC K-factor method with conductor resistance at 75 °C (copper K = 12.9, aluminium K = 21.2 ohm-circular mils per foot). It ignores reactance, which matters for large cables on AC. This is a planning tool: wire sizing must also meet ampacity and local electrical code rules, so have a qualified electrician check any installation.

    On this page

    The voltage drop calculator estimates how much voltage is lost along a cable run, from the wire size and material, the supply voltage, the load current and the length of the run. A 16-amp load on 100 feet of 12 AWG copper wire at 120 volts loses about 6.32 volts, or 5.27% of the supply, which is more than the usual 3% guideline. Moving up to 8 AWG brings the drop down to about 2.1%.

    Voltage drop matters because equipment at the end of a long run receives less voltage than the supply. Motors run hotter and less efficiently, lights dim, electronics can misbehave, and the lost voltage is wasted as heat in the cable. The calculator supports both AWG and metric mm² wire sizes, copper and aluminium conductors, and single-phase, DC and three-phase systems.

    How to use the voltage drop calculator

    1. Choose the wire size standard. Use AWG and kcmil sizes with lengths in feet, as in the United States and Canada, or mm² sizes with lengths in metres, as used in most other countries.
    2. Choose the conductor material and wire size. Copper is the most common for building wiring; aluminium is often used for larger feeders and service cables.
    3. Enter the supply voltage and choose the system. Use single-phase or DC for most household circuits, solar and battery systems, and three-phase for commercial and industrial supplies.
    4. Enter the load current in amps, and the one-way length of the cable from the supply to the load. The calculator accounts for the return path itself.
    5. Select Calculate voltage drop. You’ll see the drop in volts and as a percentage, the voltage at the load, the power lost in the cable, and the smallest listed wire size that keeps the drop at 3% or less.

    The voltage drop formula

    The calculator uses the K-factor method common in North American practice:

    • Single-phase and DC: VD = 2 × K × I × L ÷ CM
    • Three-phase: VD = 1.732 × K × I × L ÷ CM

    Here VD is the voltage drop in volts, K is the conductor’s resistivity in ohm-circular mils per foot (12.9 for copper and 21.2 for aluminium at 75 °C), I is the current in amps, L is the one-way length in feet, and CM is the conductor area in circular mils. The factor of 2 accounts for current flowing out and back on two conductors. In a balanced three-phase system, the factor is √3, about 1.732, and the result is the line-to-line drop.

    Metric sizes are converted to circular mils (1 mm² is about 1,973.5 circular mils) and metres to feet, so both systems use the same method. The result matches the resistivity approach used in metric countries: copper at 75 °C has a resistivity of about 0.0214 ohm·mm² per metre.

    Worked examples

    A long 120 V circuit

    A 16 A load is fed by 100 ft of 12 AWG copper, which has an area of 6,530 circular mils. VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, which is 5.27% of 120 V. The load receives about 113.7 V, and about 101 watts are lost as heat in the cable. With 10 AWG (10,380 circular mils) the drop falls to 3.98 V or 3.31%, and with 8 AWG to about 2.50 V or 2.08%.

    A 230 V circuit in metric sizes

    A 16 A load on 30 m of 2.5 mm² copper cable has a drop of about 8.23 V, or 3.58% of 230 V. Moving to 4 mm² cable reduces it to below 3%.

    A three-phase feeder

    A 50 A three-phase load at 240 V, fed by 200 ft of 4 AWG aluminium, has a drop of 1.732 × 21.2 × 50 × 200 ÷ 41,740 = 8.80 V, or 3.67%. The next size up, 3 AWG, brings it under 3%.

    How much voltage drop is acceptable?

    An informational note in the US National Electrical Code (NEC) recommends sizing conductors so the voltage drop is no more than 3% on a branch circuit and no more than 5% in total for the feeder and branch circuit combined. These are recommendations for efficient operation rather than mandatory rules in most cases, though some situations, such as certain equipment and fire pumps, have specific requirements. Other countries set their own limits. In the UK, for example, the wiring regulations give typical maximum drops of 3% for lighting circuits and 5% for other circuits on public supplies.

    Low-voltage systems are much more sensitive. A 1-volt drop is less than 1% of a 120 V supply but more than 8% of a 12 V supply, which is why solar, automotive, marine and LED lighting systems often need much larger cables than you’d expect for the current involved.

    Example: a 12 V solar or battery system

    Consider a 10 A load, such as a fridge or pump, 20 ft from a 12 V battery. With 10 AWG copper, the drop is 2 × 12.9 × 10 × 20 ÷ 10,380 = 0.50 V, or 4.1% of the supply. That’s already too much for many 12 V devices, which may shut off when the voltage sags. Moving to 8 AWG cuts the drop to 0.31 V (2.6%), and 6 AWG to 0.20 V (1.6%). If the same equipment ran at 24 V, it would draw only 5 A for the same power, and 10 AWG cable would give a drop of just over 1%. That’s why larger off-grid and RV systems often use 24 V or 48 V batteries.

    How to reduce voltage drop

    • Use a larger conductor. Voltage drop is inversely proportional to cross-sectional area, so going up two AWG sizes roughly halves it.
    • Shorten the run. Drop is proportional to length. Moving a panel or supply point closer to the load helps.
    • Use a higher voltage. For the same power, doubling the voltage halves the current and quarters the percentage drop. That’s one reason long runs to outbuildings or well pumps often use 240 V rather than 120 V.
    • Choose copper over aluminium for the same size, or step up an aluminium conductor by about two sizes to match copper’s performance.
    • Run parallel conductors for very large loads, where a single cable would be impractically large.

    Voltage drop and wire ampacity

    Voltage drop and ampacity are separate checks, and a cable has to pass both. Ampacity is the maximum current a conductor can carry safely without overheating, and it depends on the wire size, insulation rating, installation method and ambient temperature. A short run might easily meet the voltage drop guideline but still need a larger wire for ampacity, while a long run often needs a larger wire for voltage drop than ampacity alone would require. The calculator only covers voltage drop. Always check ampacity tables and your local electrical code, and have work on mains wiring carried out or inspected by a qualified electrician.

    Limitations of the calculation

    • Temperature: resistance rises as a conductor gets warmer. The K values here assume 75 °C, a common rating for building wire under load. A cool, lightly loaded cable will have a slightly smaller drop.
    • Reactance: on AC circuits, large conductors also have inductive reactance, which adds to the drop, especially with motor loads and in steel conduit. For cables above about 1/0 AWG or 50 mm², detailed tables that include reactance give more accurate results.
    • Power factor: the method assumes a resistive load. Motors and other inductive loads can change the result slightly.
    • Stranding and coatings: stranded and tinned conductors have slightly different resistances from the standard values.

    Related calculations

    Two other tools work well alongside this one: the ohms law calculator, to find voltage, current, resistance and power from any two values, and the resistor calculator, to decode resistor colour codes.

    Frequently asked questions

    For single-phase or DC, multiply 2 × K × current × one-way length in feet, and divide by the wire area in circular mils. K is 12.9 for copper and 21.2 for aluminium.

    The NEC recommends no more than 3% on a branch circuit and 5% in total for the feeder and branch circuit together.

    At 120 V on copper, 10 AWG gives about 4.97 V or 4.1% drop, so 8 AWG (about 2.6%) keeps it under 3%. Ampacity and code rules still apply.

    Enter the one-way length from the supply to the load. The formula already doubles it for the return conductor.

    The same voltage lost in a cable is a much larger percentage of a low supply voltage, and low-voltage systems also carry more current for the same power.

    Yes. Aluminium has about 64% higher resistance than copper of the same size, so it needs to be about two AWG sizes larger for the same drop.

    Three-phase uses √3 (1.732) instead of 2 in the formula, and the result is the line-to-line voltage drop.

    No. Ampacity is about overheating; voltage drop is about the voltage lost over distance. A wire must meet both requirements.

    About 1,973.5 circular mils.

    Yes. Choose single-phase or DC, enter the system voltage, such as 12, 24 or 48 V, and the current.